FOBAS ALERT: High Water in Fuels in Singapore

Must read

Repost: Recently FOBAS has tested a number of VLSFO samples from Singapore that exceeded the/vlimit for water as stipulated in theISO 8217:2017specification. The fuels had water ranging between0.65to1.90 %v/v.

Water at these levels would be expected to be manageable during effective onboard treatment, however would still be a concern and would also have commercial implications.

If high water is found in a bunker fuel, then further samples should be taken from the top, middle and bottom of the respective bunker tank(s) to determine the distribution of water through the tank. Further to this, samples should also be taken from before and after the purifier to determine the reduction of water to acceptable levels (/v) before engine entry.

Any carry over of water into the engine fuel rail has potential to cause damage to the fuel pumps, injectors and cylinder components as well as possible turbo charger surging and fouling.

If your ships are planning to bunker in Singapore then we suggest that the supplier is asked to provide a certificate of quality of the particular stem to ensure that the water concentration is known at the time of bunkering and within the limits of stipulated grade. Particular attention should be given to the collection of a fully representative drip samples ensuring all supporting documentation and samples drawn are witnessed and signed for by all parties present.